This internal microwave sensor adds occupancy and daylight-responsive control to a compatible VP542 vapour-tight fixture. It supports full-output illumination while a space is occupied, followed by a selected standby level and eventual switch-off, which can suit corridors and indoor parking areas within the host fixture limits.
The sensor uses 10.5–15V DC, nominally 12V, and provides a 0–10V dimming signal. Connect it only to the specified low-voltage driver supply and dimming connections; do not connect it directly to the fixture branch-circuit voltage. Keep the sensing face clear of metal shielding and away from the driver as instructed.
DIP switches provide sensitivity, hold time, daylight threshold, standby period and standby dimming settings. The separately sold VP542-RC remote offers expanded settings and commissioning controls. The manual gives a maximum ceiling mounting height of 4 m; coverage changes with mounting height, movement and site conditions.
The sensor itself is IP20 and intended for internal installation. The wet-location or IP66 rating of a VP542 fixture is not the rating of this loose sensor. The sensor operating range is -20°C to 60°C, with a documented five-year warranty. Use it in suitable indoor installations and avoid moving fixtures, nearby vibrating machinery and metal enclosures that obstruct detection. The remote and light fixture are separate items.
| Brands | Etlin-Daniels |
|---|---|
| MPN ( Part No.) | VP542-SENMC-12V |
| Voltage | 10.5–15V DC (nominal 12V) |
| Feature | Internal microwave sensor;0–10V output;5.8GHz±75MHz;<30mA;standby0.5W;IP20;maximum4m ceiling mounting;-20°C to60°C;5-year sensor warranty;DIP switches and optional VP542-RC; Product: Sensor |
| Pack Quantity | 1 |